L 2/10 230 ff 4 TT

Low Voltage Surge Protective Device

ZOTUPLIMITER

202 240 212 240 L 2-10 230 ff 4 TTprodotto

fulmine giallo grande 70request support

L 2/10 230 230 ff 4 TT is a ready to install assembly of voltage limiting SPDs providing four modes of protection, typically installed in Sub Distribution Boards (SDBs) for three-phase plus neutral 230/400 V TT-systems downstream a RCD where connection type CT1 (4) is required according to HD 60364-5-534. This SPD is suitable for three-phase plus neutral
230/400 V TN-systems too, when high performances against TOV are required.
It provides the following features and benefits:

  • Impulse test classification: Test class II according to IEC 61643-11 Ed. 1 (2011-03) and Type 2 according to
    EN 61643-11 (2012-10);
  • Backup protection is not required with an upstream CB ≤ 160 A or up to an Isccr ≤ 5 kA rms;
  • Three colour Status Indicator with progressive indication of remaining performance.

Data Sheet L 2/10 230 ff 4 TT

202 240 212 240 L 2-10 230 ff 4 TT

L 2/10 230 ff 2 TT

Low Voltage Surge Protective Device

ZOTUPLIMITER

202 220 212 220 L 2-10 230 ff 2 TTprodotto

fulmine giallo grande 70request support

L 2/10 230 ff 2 TT is a ready to install assembly of voltage limiting SPDs providing two modes of protection, typically installed in Sub Distribution Boards (SDBs) for single-phase 230 V TT-systems downstream a RCD where connection type CT1 (2) is required according to HD 60364-5-534. This SPD is suitable for single-phase 230 V TN-systems too, when high performances against TOV are required.

It provides the following features and benefits:

  • Impulse test classification: Test class II according to IEC 61643-11 Ed. 1 (2011-03) and Type 2 according to
    EN 61643-11 (2012-10);
  • Backup protection is not required with an upstream CB ≤ 160 A or up to an Isccr ≤ 5 kA rms;
  • Three colour Status Indicator with progressive indication of remaining performance.

Data Sheet L 2/10 230 ff 2 TT

202 220 212 220 L 2-10 230 ff 2 TT

 

 

ILF 4P 250/400

Low Voltage Surge Protection Device

ZOTUPFILTER

219 374 219 344 ILF 4P 250 400 PRODOTTO

fulmine giallorosso grande

 

ILF 4P 250/400 is a multimode SPD for direct and indirect lightning effects with integrated interference filter for high frequency disturbances, typically installed in in three phase plus neutral TN systems for the protection of Control Rooms, Data Centers or EDPs, with the following features and benefits:

  • Impulse test classification: Test Class I, II and III according to IEC 61643-11 Ed.1 (2011-03) and Type T1, T2 and T3 according to
    EN 61643-11(2012-10);
  • Although a special inductor ensures an effective attenuation of high frequency interferences capacity, it has an insignificant energy insertion loss if compared with the equivalent one of an insulation transformer.

Data sheet ILF 4P 250/400

219 374 219 344 ILF 4P 250 400

219 374 219 344 ILF 4P..IMG

CP

Low Voltage Surge Protective Device

ZOTUPACCESSORIES

spd accessories CP

CP 1 is an insulated extension clamp with 3 wire terminations and enables a V-connection even if the SPD
is not equipped with double clamps.

CP 1 can be assembled on the SPD's PE terminal as well as on phase or neutral terminals.

Data sheet CP

249 591 249 592...CP 1 CP 2...

 

249 591 249 592 ... CP1 CP2 SPD...

CP2 to CP8 are fork-type busbars with 2 up to 8 connection points. Typical application: to provide a common PE connection for
several SPDs. In TT system applications these busbars can also be used to provide a common neutral point connection to N-PE SPDs type I 12, I 52 and I 100.

249 591 249 592...CP 2...

ILF 2P C 16

spd with filter ILF 2P C16

 

ILF 2P C 16 is a multimode SPD for indirect lightning effects with integrated interference filter for high frequency disturbancies, for connection to single phase socket outlets to protect sensitive electronic equipment like computers, printers, switches, hubs, with the following features and benefits:

Impulse test classification: Test Class III (according to IEC 61643–1+A1) and Type 3 (according to EN 61643–11/A11);
• Providing 5 protected Schuko socket outlets with a maximum total load of 3.680 W;
• Visual indicator for the power ON-state (red light) and for the operating state of the protection circuitry (green LED);
• It is suitable for installation at LPZ boundaries 2 -3 and higher, in accordance with the lightning protection zones concept and in
coordination with other SPDs;
• Equipped with adjustable mounting brackets for 19'' racks or panels, for easy installation on the front or on the back of 19" racks.

Data sheet ILF 2P C 16

data sheet spd ILF 2P C16

 

ILF 4P ...

Low Voltage Surge Protection Device

ZOTUPFILTER

219 334 219 354 219 384 219 314 ILF 4P...SPD

ILF 4P is a multimode SPD for indirect lightning effects with integrated interference filter for high frequency disturbancies, typically installed in three phase plus neutral TN-systems close to equipment or machinery, particularly in industrial automation environment, with the following features and benefits:

  • Impulse test classification: Test Class III according to IEC 61643-11 Ed.1 (2011-03) and Type T3 according to
    EN 61643-11(2012-10);
  • Protects electronic equipment (PLC or computers, etc.) from overvoltages due to indirect lightning effects and from other interferences;
  • In case of an SPD failure the protection is disconnected without interrupting the downstream supply. The failure is indicated locally by an optical indicator and via a remote signal contact;
  • It is suitable for installation at LPZ boundaries 2 -3 and higher, in accordance with the lightning protection zones concept and in coordination with other SPDs.

Data sheet ILF 4P

219 334 219 354 219 384 219 314 ILF 4P

219 334 219 354 219 384 219 314 ILF 4PIMG..

                      

ILF 2P ...

Low Voltage Surge Protection Device

ZOTUPFILTER

219 330 219 350 219 380 ILF 2P...SPD

ILF 2P is a multimode SPD for indirect lightning effects with integrated interference filter for high frequency disturbancies, typically installed in single phase TN-systems close to equipment or machinery, particularly in industrial automation environment, with the following features and benefits:

  • Impulse test classification: Test Class III according to IEC 61643-11 Ed.1 (2011-03) and Type T3 according to
    EN 61643-11(2012-10);
  • Protects electronic equipment (PLC or computers, etc.) from overvoltages due to indirect lightning effects and from other interferences;
  • In case of an SPD failure the protection is disconnected without interrupting the downstream supply. The failure is indicated locally by an optical indicator and via a remote signal contact;
  • It is suitable for installation at LPZ boundaries 2 -3 and higher, in accordance with the lightning protection zones concept and in coordination with other SPDs.

Data sheet ILF 2P

219 330 219 350 219 380 ILF 2P

219 330 219 350 219 380 ILF 2PIMG..

ILF 2P ... DIN

Low Voltage Surge Protection Device

ZOTUPFILTER

209 310 219 310 ... ILF 2P PRODOTTO ..

ILF 2P ... DIN is a multimode SPD for indirect lightning effects with integrated interference filter for high frequency disturbancies, typically installed in single phase TN and TT systems close to equipment or machinery, particularly in industrial automation environment, with the following features and benefits:

  • Impulse test classification: Test Class III according to IEC 61643-11 Ed. 1 (2011-03) and Type 3 according to
    EN 61643–11 (2012-10);
  • Protects electronic equipment (PLC or computers, etc.) from overvoltages due to indirect lightning effects and from other interferences;
  • In case of an SPD failure the protection is disconnected without interrupting the downstream supply. The failure is indicated locally by two colours status indicator and via a remote signal contact;
  • It is suitable for installation at LPZ boundaries 2 -3 and higher, in accordance with the lightning protection zones concept and in coordination with other SPDs;
  • Upon request, ILF 2P ... DIN SPDs type can be supplied with other voltages and currents rating.

Data sheet ILF 2P DIN

209 310 219 310 209 320 219 320 209 325 219 325 ILF 2PDIN

 

209 310 209 320 209 325 219 310 219 320 219 325 ILF 2PIMG..

 

FacebookLinkedin